Preliminary acoustic calculation for the auditorium room
Auditorium acoustics are calculated based on drawing parameters (the interior space of the auditorium is bounded by rigid sound insulation walls), sound absorption coefficients (determined experimentally for the materials to be used), and international standards for measurement and design in schools ISO 354, 345, BB93, TCVN 175:2014, TCVN 355:2005.
Input parameters
Room volume
Room volume is defined as a space enclosed by sound insulation walls, considered as a sound propagation medium where energy is not lost through gaps or uncloseable openings.
This space is the stage and audience volume of the auditorium.


Determination formula:
V= [(8.65+9.16)*(20.36-16.47)/2+(9.16+7.92)*(16.47-4.93)/2+(7.92+6)*4.93/2]*22+ (10.12+15.27)*5.8*5.7/2= 4.1048e+03 m3
Carpeted floor area
The carpeted floor area is the surface area covered with gray felt according to the effect of the sound source.
Based on the two figures above, the carpeted area can be determined as follows:
Stham = [20.36-16.47 + sqrt(16.47^2+ 4.16^2) ]*22.07 = 460.76 m2
Wall area installed with foam panels
The area is determined by the total area covered by the foam layer regardless of continuity.
This area includes both side walls and the back wall of the auditorium.
This area is determined based on dimensions from the figure below.
The determination formula includes:
Smut = [(5.6+7.35)*11.09/2+(5.37+6.04)*18.06]*2+3.31*22.07= 628.79 m2

Wall area installed with perforated panels
Similar to the wall setup with foam panels, the area of the wall installed with perforated panels is also equal to the total covering area of perforated wooden panels providing sound absorption capability.
Perforated walls are installed below the absorbing foam layers.
The total wall area installed with perforated panels is determined as follows:
Slo= [3.89*3+ (1.54+3)*7.2/ 2+(1.03+1.98+1.54)*8.06/2]*2+1.98*22= 136.261 m2

Panel area on the ceiling
The ceiling will be arranged with folded sonic panels measuring 1.97 x 1.22 m. A total of 90 panels are suspended from the ceiling for the purpose of absorbing incoming sound towards the ceiling. This area is considered by the projection plane of each panel onto the floor plane.
This area is the total flat projected area of all 90 panels.
The ceiling panel area is determined as follows:
Stran= 90*1.97*1.22 = 216.3 m2

Stage curtain area
The stage curtain area is installed on both wings playing the role of natural entry and exit doors.
Due to the wide space behind, the sound absorption coefficient is considered to be 1.
The total area of this curtain region is determined:
Srem= 4.93 *5.7 * 2= 56.2 m2

Sound absorption coefficient
Foam material
Statistical table of the sound absorption coefficient of acoustic foam at different frequency bands.

Perforated material

Felt floor carpet

Flexible ceiling panel

Theoretical reverberation time
Theoretical reverberation time is the time it takes for sound energy to decay by 60 dB.
Usually, we cannot calculate RT60 directly but can only test RT20 and interpolate RT60.
The theoretical reverberation time is calculated according to the material coefficients, room volume, and surface area above.
Sabine's formula: (Reverberation time at 500 Hz and 1 kHz decays by 60 dB)
RT60_500= 0.16*V/Sα(500) =0.6889 (seconds).
RT60_1000= 0.16*V/Sα(1000) =0.6335 (seconds).
Theoretical reverberation time without using flexible ceiling panels
When ceiling panels are not used, the change will be in the Sα coefficient (total absorption area) according to Sabine's formula.
At that time, Sα will be determined:
Sα = S_carpet * α_carpet + S_foam * α_foam + S_opening * α_opening + S_curtain * α_curtain
= 797 m2
Sabine's formula: (Reverberation time at 500 Hz and 1 kHz decays by 60 dB)
RT60_500= 0.16*V/Sα(500) =0.8291 (seconds).
RT60_1000= 0.16*V/Sα(1000) =0.7519 (seconds).
Vietnamese standard reverberation time
Based on standard 355:2005. The reverberation time will be applied according to the following chart:

Interpolating line number 6 with a volume of 4.1e3 m3, the ideal reverberation time will be 0.85 seconds.
International standard reverberation time

The coefficient is determined to be 0.8 s for the new auditorium and with curtains according to THE ACOUSTIC DESIGN OF A MULTIPURPOSE HALL from Finland.
Conclusion 1:
The theoretical calculated reverberation time (RT60) (when including the absorbent ceiling) is smaller than the ideal time required by standard 355:2005 and [TO BE ADDED: ...]. Compliance achieved.
The theoretical calculated reverberation time (RT60) (when excluding the absorbent ceiling) meets the requirements of standard 355:2005.
The theoretical calculated reverberation time (RT60) (when excluding the absorbent ceiling) at 500 Hz does not comply with the international standard because the reverberation time (RT60) is greater than 0.8 s.
The theoretical calculated reverberation time (RT60) (when excluding the absorbent ceiling) at 1000 Hz complies with the international standard because the reverberation time (RT60) is only 0.75 s, which is smaller than the 0.8 s required by the standard.
VILAS 1541 · ISO/IEC 17025
Need advice on Materials Acoustic Testing?
Services of testing, measuring and analyzing acoustic properties of equipment, products, vehicles, acoustic materials, etc.
Related Articles
Articles from the same category or related topics
- 6 min read
From Vietnamese Acoustic Knowledge to International Forums: DASM's Research Milestone in Acoustics Australia
A research paper on acoustic materials by DASM was published in Acoustics Australia, a world-renowned acoustic journal, marking a new step forward for DASM in the field of acoustics
Read more → - 3 min read
DASM Sound Absorption Testing for Noise Barriers According to ISO 354:2024 & EN ISO 11654:1997
DASM sound absorption testing for Noise Barriers in a reverberation room according to ISO 354:2024 and EN ISO 11654:1997 standards at a VILAS-certified laboratory
Read more → - 4 min read
DASM Participates in Long-Span Bridge Workshop for High-Speed Railways – Expanding Research Capabilities in Acoustics and Structural Vibration
DASM participates in the long-span bridge workshop for high-speed railways to update structural design trends, control structural vibration and acoustics, and prepare capabilities for projects
Read more →